Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL02082
Parcel: 125111270

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T10EL02082
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved