Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10EL02048
Parcel: 11106008A

Review Status: Active

Review Details: ELECTRICAL

Permit Number - T10EL02048
Review Name: ELECTRICAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2010 ANY ELECTRICAL-RESIDENTIAL REVIEW Active