Permit Number: T10EL02026
Parcel: 10602242A

Address:
3782 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL02026
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are comments for the lighting modification & electrical repair
submittal for COT ID# 491 at 3782 North Oracle Road (T10EL02026).

Sheet 1 of 8

No comments.

Sheet 2 of 8

No comments.

Sheet 3 of 8

1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly.

2. In Note #2 as the THHN conductors, add unless otherwise indicated.

3. Partial Plan View: depict conductors between panel and first junction
box (particularly to show at which of the two east junction boxes the
incoming connection is made).

4. Panel Schedule & New One-Line Diagram: resolve the inconsistency on the
panel ratings (100A vs. 60A).

Sheet 4 of 7

No comments.

Sheet 5 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 4 for IES File 103328_L.

Sheet 6 of 7

No comments.

Sheet 7 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 6 for IES File 103328_R.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2010 CPIERCE1 OUT TO CUSTOMER Completed
10/01/2010 SUE REEVES REJECT SHELF Completed