Permit Number: T10EL01820
Parcel: 305070080

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01820
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Comments below are for the lighting relocation & electrical repair
resubmittal for COT ID# 589 at 11401 East I-10 (T10EL01820).

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Title Block: add Stipulation address (11401 E. I-10) (no objection if
this is added with the permission of the EOR or administratively).

2. Comment for futre reference: Electrical Riser Diagram and One-Line
Diagram: depict the Profile 2000 clock box that is separately wired into the
disconnect (in addition to the old in line clock box).

3. Comment for future refrence: include panel schedule.

Sheet 3 of 3

1. Title Block: add Stipulation address (11401 E. I-10) (no objection if
this is added with the permission of the EOR or administratively).
09/07/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/07/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/29/2010 CINDY AGUILAR OUT TO CUSTOMER Completed