Permit Number: T10EL01820
Parcel: 305070080

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01820
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/28/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/28/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/10/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting relocation & electrical repair submittal
for COT ID# 589 at 11401 East I-10 (T10EL01820). If junction box is to be
used between the two new ballasts, that must be shown on the plan.

Sheet 1 of 3

1. Depict south property line of subject property (also section line).

Sheet 2 of 3

1. Title Block: add Stipulation address (11401 E. I-10).

2. Partial Vicinity Map: depict existing disconnect and clock box at
correct location (north pole).

3. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

5. One-Line Diagram: depict and include circuitry for ballasts, clock box
and any other fixtures where wire connections are made.

Sheet 3 of 3

1. Title Block: add Stipulation address.

2. Include full specs for new ballast (as in other submittals).

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2010 CPIERCE1 OUT TO CUSTOMER Completed