Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC10days
Permit Number - T10EL01820
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/28/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/10/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Comments below are for the lighting relocation & electrical repair submittal for COT ID# 589 at 11401 East I-10 (T10EL01820). If junction box is to be used between the two new ballasts, that must be shown on the plan. Sheet 1 of 3 1. Depict south property line of subject property (also section line). Sheet 2 of 3 1. Title Block: add Stipulation address (11401 E. I-10). 2. Partial Vicinity Map: depict existing disconnect and clock box at correct location (north pole). 3. Notes: add notation that any excess fixtures, conduit, connectors, wiring, or breakers no longer being used to be removed. 4. Notes: add notation that no junction boxes or other fixtures where wire connections are made to be installed or remain on the load side of the panel other than those depicted on the plan. 5. One-Line Diagram: depict and include circuitry for ballasts, clock box and any other fixtures where wire connections are made. Sheet 3 of 3 1. Title Block: add Stipulation address. 2. Include full specs for new ballast (as in other submittals). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/19/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |