Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01798
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/21/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are amended comments for the lighting modification & electrical repair
submittal for COT ID# 299 at 2005 South Alvernon Way (T10EL01798). The
amendments are subsequent to review of the applicant's 9/14/10 response
letter (submitted 9/14/10).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless noted otherwise to Note #2 on THHN conductors.

3. Add note: "Only electrical fixtures and devices indicated may be altered or remain on billboard.

4. Add standardized notation on special inspection requirement for metal
halide lighting installation.

5. Partial Vicinity Map and Partial Plan View: show existing junction box
to remain and note new ½" EMT after (as distinct from existing ¾" EMT before
the existing junction box).

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2010 SUE REEVES APPROVAL SHELF Completed
10/22/2010 CPIERCE1 OUT TO CUSTOMER Completed