Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC30days
Permit Number - T10EL01798
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/21/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/22/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | Below are amended comments for the lighting modification & electrical repair submittal for COT ID# 299 at 2005 South Alvernon Way (T10EL01798). The amendments are subsequent to review of the applicant's 9/14/10 response letter (submitted 9/14/10). Sheet 1 of 4 No comments. Sheet 2 of 4 No comments. Sheet 3 of 4 1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly. 2. Add unless noted otherwise to Note #2 on THHN conductors. 3. Add note: "Only electrical fixtures and devices indicated may be altered or remain on billboard. 4. Add standardized notation on special inspection requirement for metal halide lighting installation. 5. Partial Vicinity Map and Partial Plan View: show existing junction box to remain and note new ½" EMT after (as distinct from existing ¾" EMT before the existing junction box). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2010 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/22/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |