Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10EL01798
Parcel: 13018088K

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01798
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/27/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/23/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the 7/23/10 lighting modification & electrical repair
submittal for COT ID# 299 at 2005 South Alvernon Way (T10EL01798).

Sheet 1 of 4

No comments.

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment as part of
plan set (May 20, 2010; June 9, 2010 revisions).

Sheet 3 of 4

1. Notes (Bullet #5) & Elevation: reduce the number of #12 replacement
conductors between the existing junction box and the first junction box
(south face) from six (6) to three (3); number of existing conductors to be
field confirmed.

2. Notes (Bullet #7) & Partial Plan View: reduce the number of #12
replacement conductors between the first new junction box and the next new
junction box going to the north face from three (3) to two (2).

3. Notes (Bullet #9): resolve inconsistency of use of SOOW flex cable shown
on Partial Plan View and Manufacturer's Spec Sheet with rigid connection
(3/4" nipple) between support arm and junction box described in this bullet;
clarify any need to use SOOW flex cable if entirely housed within conduit;
if exposed SOOW flex cable is to be used, add notation specifying minimum
and maximum distances below junction boxes that flex cable drip loops/slack
is to extend (or otherwise provide appropriate limit on length of flex
cables).

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

5. Panel Schedule: correct volt-amp entry for 320 watt light fixtures
(entries appear to correspond to 400-watt fixtures).

6. Panel Schedule, Partial Plan View, Elevation & One-Line Diagram: change
number of circuits from two per face to one per face.

7. Partial Vicinity Map and Partial Plan View: show existing junction box
to remain and note new ½" EMT after (as distinct from existing ¾" EMT before
the existing junction box).

8. Add notation: "Special inspection required prior to final inspection for
installation of light fixture support arms, light fixtures, shields,
gaskets, and associated parts. Inspector to verify that light fixtures are
installed with shield in a horizontal position so that no light is emitted
above the horizontal plane and that mean lumen output of the light fixtures
does not exceed 1000 lumens per horizontal foot of billboard face, as per
the City of Tucson/Pima County Outdoor Lighting Code and the City of
Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No.
C20003712)".

Sheet 4 of 4

No comments.