Permit Number: T10EL01797
Parcel: 99999999B

Address:
10603 E I10

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01797
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/13/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Comments below are for the lighting relocation & electrical repair
resubmittal (9/1/10) for COT ID# 597 at 10401 East I-10 (West) (T10EL01797).

Sheet 2 of 3

1. Title Block: add Stipulation address (10401 E. I-10 (W)) [Comment #1,
8/9/10]

2. Panel Schedule: correct the new volt-amp entry for Circuit #1 and
associated sums; based on the ballast manufacturer's stated input watts (248
watts per two lamp fixture (F96T12HO)) and the 125% continuous load factor
that the EOR is including in the panel schedule, this figure should be 620
v-a for this circuit (plus appropriate allowance for the timer); if
otherwise, provide the calculations as to how the v-a entry was arrived at;
these entries need to be standardized for all pending and future panel
schedules.

3. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed. [Comment #3, 8/9/10]

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan. [Comment #4, 8/9/10]

Sheet 3 of 3 [Not Resubmitted]

1. Title Block: add Stipulation address (10401 E. I-10 (W)). [Comment #1,
8/9/10]
10/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2010 SUE REEVES APPROVAL SHELF Completed
10/14/2010 CPIERCE1 OUT TO CUSTOMER Completed