Permit Number: T10EL01795
Parcel: 99999999B

Address:
9801 E I10

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01795
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/27/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/03/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 593 at 9801 East I-10 (T10EL01795). If junction box
is to be used between the two new ballasts, that must be shown on the plan.

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Comment for future reference: Notes: add notation that any excess
fixtures, conduit, connectors, wiring, or breakers no longer being used to
be removed.

2. Comment for future reference: Notes: add notation that no junction boxes
or other fixtures where wire connections are made to be installed or remain
on the load side of the panel other than those depicted on the plan.

3. Comment for future reference: Panel Schedule: provide correct amperage
rating and dimensions for the Sangamo panel;clarify if the timer and
photocell have dedicated circuits or are wired into the fluorescent fixture
circuit (and adjust volt-amps as necessary).

4. Comment for future reference: One-Line Diagram: depict and include
circuitry for ballasts, clock box and any other fixtures where wire
connections are made.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2010 SUE REEVES APPROVAL SHELF Completed
08/05/2010 CINDY AGUILAR OUT TO CUSTOMER Completed