Permit Number: T10EL01794
Parcel: 122161030

Address:
3728 E GRANT RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01794
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/27/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/09/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 432 at 3728 East Grant Road (T10EL01794).

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Electrical Riser Diagram & Elevation: correct or clarify the number and
gauge of conductors between the ballasts and the light fixtures, which both
appear to be inconsistent with standard ballast wire installation (no
objection to PDSD staff making correction with permission of the EOR).

2. Panel Schedule: correct the dimensions and amperage rating for the 122
panel (no objection to PDSD staff making correction with permission of the
EOR).

3. Comment for future reference: Notes: add notation that no junction boxes
or other fixtures where wire connections are made to be installed or remain
on the load side of the panel other than those depicted on the plan.

4. Comment for future reference: Notes: add notation that any excess
fixtures, conduit, connectors, wiring, or breakers no longer being used to
be removed.

5. Comment for future reference: One-Line Diagram: depict ballasts and any
other fixtures where wire connections are made.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
08/31/2010 SUE REEVES REJECT SHELF Completed