Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10EL01792
Parcel: 99999999B

Address:
4862 S 12TH AV

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01792
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/27/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/09/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Comments below are for the lighting relocation & electrical repair submittal
for COT ID# 153 at 4862 South 12th Avenue (T10EL01792). If junction box is
to be used between the two new ballasts, that must be shown on the plan.

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Comment for future reference: Notes: add notation that any excess
fixtures, conduit, connectors, wiring, or breakers no longer being used to
be removed.

2. Comment for future reference: Notes: add notation that no junction boxes
or other fixtures where wire connections are made to be installed or remain
on the load side of the panel other than those depicted on the plan.

3. Comment for future reference: One-Line Diagram: depict and include
circuitry for ballasts, clock box and any other fixtures where wire
connections are made.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/11/2010 SUE REEVES APPROVAL SHELF Completed
08/11/2010 DELMA ROBEY OUT TO CUSTOMER Completed