Permit Number: T10EL01584
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01584
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Comments below are for the lighting modification & electrical repair
resubmittal for COT ID# 325 at 4678 East Broadway Boulevard (T10EL01584).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly.

2. In Note #2 as the THHN conductors, add unless otherwise indicated.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2010 SUE REEVES OUT TO CUSTOMER Completed
10/01/2010 SUE REEVES REJECT SHELF Completed