Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10EL01584
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01584
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/09/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
07/29/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 325 at 4678 East Broadway Boulevard (T10EL01584).

Sheet 1 of 4

No comments.

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment as part of
plan set (May 20, 2010; June 9, 2010 revisions).

Sheet 3 of 4

1. Notes (Bullet #4), Existing Electrical Riser Diagram & Elevation: reduce
the number of #12 replacement conductors between the panel and first
junction box from six (6) or five (5), as applicable, to three (3); number
of existing conductors to be field confirmed.

2. Notes (Bullet #6) & Partial Plan View: reduce the number of #12
replacement conductors between the first junction box and the next junction
box going to the second face from three (3) to two (2).

3. Notes (Bullet #8): resolve inconsistency of use of SOOW flex cable shown
on Partial Plan View and Manufacturer's Spec Sheet with rigid connection
(3/4" nipple) between support arm and junction box; clarify any need to use
SOOW flex cable if entirely housed within conduit; if exposed SOOW flex
cable is to be used, add notation specifying minimum and maximum distances
below junction boxes that flex cable drip loops/slack is to extend (or
otherwise provide appropriate limit on length of flex cables).

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

5. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

6. Elevation: at first junction box, add note that branch to second (east
or west) face occurs here.

7. Elevation: indicate location of SOOW flex cable (if used).

8. Elevation: depict existing ballasts with notation to be removed.

9. Panel Schedule: correct volt-amp entry for 320 watt light fixtures
(entries appear to correspond to 400-watt fixtures).

10. Panel Schedule, Partial Plan View, Elevation & One-Line Diagram: change
number of circuits from two per face to one per face.

11. Add notation: "Special inspection required prior to final inspection
for installation of light fixture support arms, light fixtures, shields,
gaskets, and associated parts. Inspector to verify that light fixtures are
installed with shield in a horizontal position so that no light is emitted
above the horizontal plane and that mean lumen output of the light fixtures
does not exceed 1000 lumens per horizontal foot of billboard face, as per
the City of Tucson/Pima County Outdoor Lighting Code and the City of
Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No.
C20003712)".

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2010 DELMA ROBEY OUT TO CUSTOMER Completed
08/27/2010 SUE REEVES REJECT SHELF Completed