Permit Number: T10EL01575
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01575
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are for the lighting modification & electrical repair resubmittal for
COT ID# 147 at 1300 West Valencia Road (T10EL01575).

Sheet 2 of 4

1. Panel Schedule: correct the volt-amp entries for Circuits #1 and #3 and
associated sums; for Circuit #1, this figure should be 620 v-a (or rounded
up), based on the ballast manufacturer's stated input watts (248 watts per
two lamp fixture (F96T12HO)) and the 125% continuous load factor that the
EOR is including in the panel schedule; for Circuit #3 this figure should be
1167.5 v-a (or rounded up), based on the ballast manufacturer's stated input
watts (467 watts per two lamp fixture (F96T12VHO)) and the 125% continuous
load factor that the EOR is including in the panel schedule; if otherwise,
provide the calculations as to how the v-a entry was arrived at.


Sheet 3 of 4

No comments.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2010 SUE REEVES APPROVAL SHELF Completed
10/14/2010 CPIERCE1 OUT TO CUSTOMER Completed