Permit Number - T10EL01575
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/13/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/14/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | Below are for the lighting modification & electrical repair resubmittal for COT ID# 147 at 1300 West Valencia Road (T10EL01575). Sheet 2 of 4 1. Panel Schedule: correct the volt-amp entries for Circuits #1 and #3 and associated sums; for Circuit #1, this figure should be 620 v-a (or rounded up), based on the ballast manufacturer's stated input watts (248 watts per two lamp fixture (F96T12HO)) and the 125% continuous load factor that the EOR is including in the panel schedule; for Circuit #3 this figure should be 1167.5 v-a (or rounded up), based on the ballast manufacturer's stated input watts (467 watts per two lamp fixture (F96T12VHO)) and the 125% continuous load factor that the EOR is including in the panel schedule; if otherwise, provide the calculations as to how the v-a entry was arrived at. Sheet 3 of 4 No comments. Sheet 4 of 4 No comments. |