Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC30days
Permit Number - T10EL01575
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/09/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | NO ENGINEERING OR LETTER FROM ENGINEER PROVIDED FOR 3/4" RIGID CONDUIT BENT AT 90 DEGREES TO SUPPORT FIXTURES. TWO IDENTICAL PAGES IN ONE SET (3 OF 4 AND 4 OF 4) MISSING PAGE 2 OF 4 IN SECOND SET. [SHOULD HAVE 2 SETS OF 3 PAGES] |
07/09/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | MISSING PAGE 2 OF 3 IN SECOND SET OF DRAWINGS PANEL SCHEDULE INDICATES USE OF 4 CIRCUITS, BUT ONE-LINE, RISER AND ELEVATION PLANS INDICATE USING ONLY 2 CIRCUITS. |
07/29/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Comments below are for the lighting modification & electrical repair submittal for COT ID# 147 at 1300 West Valencia Road (T10EL01575). Sheet 1 of 4 No comments. Sheet 2 of 4 1. Notes (Bullet #13), Electrical Riser Diagram, West Elevation Rear View & East Elevation Front View: clarify the number of replacement riser conduit on the load side of the panel (one or two) and the number of replacement conductors therein; number of existing conductors to be field confirmed. 2. Notes: add notation that no junction boxes or other fixtures where wire connections are made to be installed or remain on the load side of the panel other than those depicted on the plan. 3. Notes: add notation that any excess fixtures, conduit, connectors, wiring, or breakers no longer being used to be removed. 4. West Elevation Rear View & East Elevation Front View: correct number of #18 wires (from 5 to 6). 5. West Face Elevation & East Face Elevation: clarify whether an additional junction box will be added or not with each of the new ballasts 6. Panel Schedule, East Elevation Front View & One-Line Diagram: change number of circuits from two per face panel to one per face panel. 7. One-Line Diagram: depict ballasts. 8. Title Block: add Stipulation address. Sheet 3 of 4 1. Title Block: add Stipulation address. Sheet 4 of 4 1. Rear Elevation West Face: clarify whether an additional junction box will be added or not with each of the new ballasts. 2. Rear Elevation West Face: reduce number of replacement conductors from four to three (3). 3. Title Block: add Stipulation address. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/08/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
09/08/2010 | SUE REEVES | REJECT SHELF | Completed |