Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL01567
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01567
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/04/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/20/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are amended comments for the lighting modification & electrical repair
submittal for COT ID# 129 at 8512 East Broadway Boulevard (T10EL01567). The
changes are subsequent to review of the applicant's 9/3/10 response letter
(submitted 9/8/10).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless otherwise indicated to Note #2 on THHN conductors.

3. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

4. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

5. Partial Plan View: depict conductors between panel and first junction
box (particularly to show at which of the two east junction boxes the
incoming connection is made).

6. For future reference: Add notation: "Special inspection required prior to final inspection, as per
the City of Tucson/Pima County Outdoor Lighting Code and the City of
Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No.
C20003712)".

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2010 SUE REEVES APPROVAL SHELF Completed
10/21/2010 CINDY AGUILAR OUT TO CUSTOMER Completed