Permit Number: T10EL01565
Parcel: 13219019B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01565
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are comments for the lighting modification & electrical repair
resubmittal for COT ID# 275 at 4620 South Country Club Road (T10EL01565).
[Note: Comments #3-#6 on Sheet 3 below were previously provided on the
initial submittal on 7/28/10, but the resubmittal was not responsive and are
provided again].

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless otherwise indicated to Note #2 on THHN conductors.

3. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

4. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2010 SUE REEVES APPROVAL SHELF Completed
10/14/2010 CPIERCE1 OUT TO CUSTOMER Completed