Permit Number: T10EL01562
Parcel: 13803031K

Review Status: Active

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01562
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/04/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/20/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are amended comments for the lighting modification & electrical repair
submittal for COT ID# 569 at 6390 South Santa Clara Avenue (T10EL01562).
The changes are subsequent to review of the applicant's 9/2/10 response
letter (submitted 9/8/10).

Sheet 1 of 4

No comments.

Sheet 2 of 4

1. Scope of Work (Bullet #1): correct configuration of existing fixtures
(existing fixtures are top-mounted).

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless otherwise indicated to Note #2 on THHN conductors.

3. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

4. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

5. For future reference: Add notation: "Special inspection required prior to final inspection, as per the City of Tucson/Pima County Outdoor Lighting Code and the City of Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No. C20003712)".

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2010 SUE REEVES APPROVAL SHELF RECEIVED