Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC30days
Permit Number - T10EL01561
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | Preliminary Comments Below are comments for the lighting modification & electrical repair resubmittal for COT ID# 78 at 4525 East 22nd Street (T10EL01561). Sheet 3 of 4 1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly. 2. Add unless noted otherwise to Note #2 on THHN conductors. 3. Add note: "Only electrical fixtures and devices indicated may be altered or remain on billboard. 4. Notes: add notation that any excess fixtures, conduit, connectors, wiring, or breakers no longer being used to be removed. 5. Add standardized notation on special inspection requirement for metal halide lighting installation. |
| 10/08/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/08/2010 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/08/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |