Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01561
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/07/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/07/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
07/29/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 78 at 4525 East 22nd Street (T10EL01561).

Sheet 1 of 4

No comments.

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment as part of
plan set (January 20, 2010; June 15, 2010 revisions).

Sheet 3 of 4

1. Notes (Bullet #4), Existing Electrical Riser Diagram & Elevation: reduce
the number of #12 replacement conductors between the panel and first
junction box from six (6) to three (3); number of existing conductors to be
field confirmed.

2. Notes (Bullet #5) & Partial Plan View: resolve inconsistency in number
of #12 replacement conductors between the first junction box and the next
junction box going to the second face from three (3) to two (2).

3. Notes (Bullet #8): if timer is internal to 206 panel and not a separate
unit, delete "and clock box".

4. Notes (Bullet #10): resolve inconsistency of use of SOOW flex cable
shown on Partial Plan View and Manufacturer's Spec Sheet with rigid
connection (3/4" nipple) between support arm and junction box; clarify any
need to use SOOW flex cable if entirely housed within conduit; if exposed
SOOW flex cable is to be used, add notation specifying minimum and maximum
distances below junction boxes that flex cable drip loops/slack is to extend
(or otherwise provide appropriate limit on length of flex cables).

5. Notes: add standard bullet on two (2) #12 conductors between light
fixtures on each face.

6. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

7. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

8. Elevation: at first junction box, add note that branch to second (east
or west) face occurs here.

9. Elevation: indicate location of SOOW flex cable (if used).

10. Panel Schedule: correct volt-amp entry for 320 watt light fixtures
(entries appear to correspond to 400-watt fixtures).

11. Panel Schedule, Partial Plan View, Elevation & One-Line Diagram: change
number of circuits from two per face to one per face.

12. One-Line Diagram & Partial Vicinity Map: show existing disconnect at
meter and amperage rating.

13. Add notation: "Special inspection required prior to final inspection
for installation of light fixture support arms, light fixtures, shields,
gaskets, and associated parts. Inspector to verify that light fixtures are
installed with shield in a horizontal position so that no light is emitted
above the horizontal plane and that mean lumen output of the light fixtures
does not exceed 1000 lumens per horizontal foot of billboard face, as per
the City of Tucson/Pima County Outdoor Lighting Code and the City of
Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No.
C20003712)".

Sheet 4 of 4

No comments.