Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01545
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/01/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
07/26/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Comments below are for the lighting modification & electrical repair
submittal for COT ID# 11 at 2451 East Benson Highway (T10EL01545).

Sheet 1 of 4

No comments.

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment as part of
plan set (January 20, 2010; June 15, 2010 revisions).

Sheet 3 of 4

1. Notes (Bullet #3), Existing Electrical Riser Diagram & Elevation: reduce
the number of #12 replacement conductors between the panel and first
junction box from six (6) to three (3); number of existing conductors to be
field confirmed.

2. Notes (Bullet #4), Elevation & Partial Plan View: reduce the number of
#12 replacement conductors between the first junction box and the second
pair of junction boxes from three (3) to two (2).

3. Notes (Bullet #7): resolve inconsistency of use of SOOW flex cable shown
on Partial Plan View and Manufacturer's Spec Sheet with rigid connection
(3/4" nipple) between support arm and junction box; clarify any need to use
SOOW flex cable if entirely housed within conduit; if exposed SOOW flex
cable is to be used, add notation specifying minimum and maximum distances
below junction boxes that flex cable drip loops/slack is to extend (or
otherwise provide appropriate limit on length of flex cables).

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

5. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

6. Notes: add notation: "Lighting and electrical configuration for 2nd
face is same as depicted for 1st face".

7. Elevation: at first junction box, add note that branch to second face
occurs here.

8. Elevation: indicate location of SOOW flex cable (if used).

9. Elevation: depict existing ballasts with notation to be removed.

10. Panel Schedule: correct panel amperage rating.

11. Panel Schedule & Partial Plan View: change number of circuits from two
per face to one per face.

12. Existing One-Line Diagram: indicate number and amperage of breakers in
existing 206 panel.

13. Shield Diagram: depict in top-down configuration with notation: "Zero
Uplight Above 90 Degrees From Nadir Ref IES File #104313" (see EDC
submittals).

14. Add notation: "Special inspection required prior to final inspection
for installation of light fixture support arms, light fixtures, shields,
gaskets, and associated parts. Inspector to verify that light fixtures are
installed with shield in a horizontal position so that no light is emitted
above the horizontal plane and that mean lumen output of the light fixtures
does not exceed 1000 lumens per horizontal foot of billboard face, as per
the City of Tucson/Pima County Outdoor Lighting Code and the City of
Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No.
C20003712)".

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/27/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
09/27/2010 SUE REEVES REJECT SHELF Completed