Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10EL01544
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01544
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/01/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/09/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Comment #12 on Sheet 3 below is withdrawn.

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 282 at 3646 South Campbell Avenue (T10EL01544).

Sheet 1 of 4

1. Comment for future reference: Title Block: change "Relocation" in title
to "Modification".

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment as part of
plan set (January 20, 2010; June 15, 2010 revisions).

Sheet 3 of 4

1. Notes (Bullet #3), Existing Electrical Riser Diagram & Elevation: reduce
the number of #12 replacement conductors between the panel and first
junction box from six (6) to three (3); number of existing conductors to be
field confirmed.

2. Notes (Bullet #4): reduce the number of #12 replacement conductors
between the first junction box and the second pair of junction boxes from
three (3) to two (2); show same on Elevation.

3. Notes (#12): resolve inconsistency of use of SOOW flex cable shown on
Partial
Plan View and Manufacturer's Spec Sheet with rigid connection (3/4" nipple)
between support arm and junction box; clarify any need to use SOOW flex
cable if entirely housed within conduit; if exposed SOOW flex cable is to be
used, add notation specifying minimum and
maximum distances below junction boxes that flex cable drip loops/slack is
to extend (or otherwise provide appropriate limit on length of flex cables).

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

5. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

6. Elevation: at first junction box, add note that branch to second face
occurs here.

7. Elevation: indicate location of flex cable loops between junction boxes
and light fixtures.

8. Elevation: depict existing ballasts with notation to be removed.

9. Panel Schedule: correct panel amperage rating.

10. Panel Schedule & Partial Plan View: change number of circuits from two
per face to one per face.

11. Existing Electrical Riser Diagram: indicate number and amperage of
breakers in
existing 206 panel.

12. New One-Line Diagram: the #4 bond to ground rods is oversized as to
existing and NEC minimum; either reduce to #8 or clarify need for oversized
bond.

13. Title Block: correct the address to match Stipulation.

14. Shield Diagram: depict in top-down configuration with notation: "Zero
Uplight Above 90 Degrees From Nadir Ref IES File #104313" (see EDC
submittals).

15. Add notation that as per Subparagraph 8.3.4 of the Stipulation a
special inspection is to be performed for metal halide lighting compliance
as provided for in Section 306 of the 1997 Uniform Administrative Code (or
any applicable successors or amendments thereto).

Sheet 4 of 4

1. Title Block: correct the address to match Stipulation.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/09/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
08/09/2010 SUE REEVES REJECT SHELF Completed