Permit Number: T10EL01543
Parcel: 11518023A

Address:
1333 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01543
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Comments below are for the lighting modification & electrical repair for COT ID# 511 at 1333 North Oracle Road
(T10EL01543).

Sheet 1 of 4

No comments

Sheet 2 of 4

No comments

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly.

2. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

3. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

4. In Note #2 as the THHN conductors, add unless otherwise indicated.

5. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly.

6. Existing One-Line Diagram: indicate number and amperage of breakers in
existing 122 panel.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/01/2010 SUE REEVES OUT TO CUSTOMER Completed
10/01/2010 SUE REEVES REJECT SHELF Completed