| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/13/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 09/30/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/01/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | Comments below are for the lighting modification & electrical repair for COT ID# 511 at 1333 North Oracle Road (T10EL01543). Sheet 1 of 4 No comments Sheet 2 of 4 No comments Sheet 3 of 4 1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly. 2. Notes: add notation that no junction boxes or other fixtures where wire connections are made to be installed or remain on the load side of the panel other than those depicted on the plan. 3. Notes: add notation that any excess fixtures, conduit, connectors, wiring, or breakers no longer being used to be removed. 4. In Note #2 as the THHN conductors, add unless otherwise indicated. 5. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly. 6. Existing One-Line Diagram: indicate number and amperage of breakers in existing 122 panel. Sheet 4 of 4 No comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/01/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |
| 10/01/2010 | SUE REEVES | REJECT SHELF | Completed |