Permit Number: T10EL01543
Parcel: 11518023A

Address:
1333 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01543
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
07/01/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
07/29/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 511 at 1333 North Oracle Road (T10EL01543). Note:
this submittal was provided on June 28 without noting the July 26 deadline
for comments or the date of submittal.

Sheet 1 of 4

1. Correct the billboard footprint, which is further to the west of the
east property line.more than the 3-foot tolereance allows for.

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment as part of
plan set (May 20, 2010; June 9, 2010 revisions).

Sheet 3 of 4

1. Notes (Bullet #6), Existing Electrical Riser Diagram & Elevation: reduce
the number of #12 replacement conductors between the panel and first
junction box from six (5) to three (3); number of existing conductors to be
field confirmed.

2. Notes (Bullet #8), Elevation & Partial Plan View: reduce the number of
#12 replacement conductors between the first junction box and the second
junction box from three (3) to two (2).

3. Notes (Bullet #10): resolve inconsistency of use of SOOW flex cable
shown on Partial Plan View and Manufacturer's Spec Sheet with rigid
connection (3/4" nipple) between support arm and junction box; clarify any
need to use SOOW flex cable if entirely housed within conduit; if exposed
SOOW flex cable is to be used, add notation specifying minimum and maximum
distances below junction boxes that flex cable drip loops/slack is to extend
(or otherwise provide appropriate limit on length of flex cables).

4. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

5. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

6. Elevation: at first junction box, add note that branch to 12.25x24.5
face occurs here.

7. Elevation: indicate location of SOOW flex cable (if used).

8. Elevation: depict existing ballasts on 14x48 side with notation to be
removed.

9. Panel Schedule: correct panel amperage rating.

10. Panel Schedule & Partial Plan View: change number of circuits on 14x48
side from two per face to one per face.

11. Existing One-Line Diagram: indicate number and amperage of breakers in
existing 122 panel.

12. Shield Diagram: depict in top-down configuration with notation: "Zero
Uplight Above 90 Degrees From Nadir Ref IES File #104313" (see EDC
submittals).

13. Add notation: "Special inspection required prior to final inspection
for installation of light fixture support arms, light fixtures, shields,
gaskets, and associated parts. Inspector to verify that light fixtures are
installed with shield in a horizontal position so that no light is emitted
above the horizontal plane and that mean lumen output of the light fixtures
does not exceed 1000 lumens per horizontal foot of billboard face, as per
the City of Tucson/Pima County Outdoor Lighting Code and the City of
Tucson-Clear Channel Outdoor Stipulation (Pima County Superior Court No.
C20003712)".

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/27/2010 DELMA ROBEY OUT TO CUSTOMER Completed
08/27/2010 SUE REEVES REJECT SHELF Completed