Permit Number: T10EL01285
Parcel: 114462120

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01285
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project; T10EL01285
7801 E Wrighstown Rd

Electrical denied,
1. The plans do not show the conversion fron the junction box to the support pipe which the SOOW Cable or the UF Cable go through, then the conversion from the support pipe to a different raceway then into the fixture.
2. Does the fixture provide a threaded hub ?
3. From what documention is the lumen count for the 320W MH fixture obtained.

Ray T Majuta
City of Tucson PDSD,
Elect Pln Ck
6/2/10
Ray.Majuta@tucsonaz.gov
06/02/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: REFERENCE EXHIBIT 9 FOR REPLACEMENT OF ITEMS INDICATED ON SHEET 2. VERIFY NEW C6X10.5 MOUNTING BRACKETS, NEW 2.875" DIAMETER PIPES, NEW 2.375" DIAMETER PIPE LIGHT ARMS, NEW STIFFENER PLATES, AND NEW LIGHT FIXTURES ARE ALLOWED AS AUTHORIZED REPAIRS AND ALTERATIONS.
2. GENERAL: REPAIRS INDICATED FOR THIS BILLBOARD WILL BE DISCUSSED AT A FUTURE MEETING. APPROVAL OF THIS PROJECT WILL BE WITHHELD UNTIL THAT MEETING.
3. SHEET 1; BILLBOARD NOTES 7: REFERENCE IS MADE TO SHEET 2 OF 3. THERE ARE 4 TOTAL SHEETS. REVISE NOTE.
4. SHEET 1; BILLBOARD NOTES 9: REVIEW ALL PARAGRAPH REFERENCES LISTED AND VERIFY THOSE RELATE TO THE WORK DESCRIBED ON SHEET 2. REVISE REFERENCES AS REQUIRED.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/30/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Comments below are for the lighting modification & electrical repair
submittal for COT ID# 119 at 7801 East Wrightstown Road (T10EL01285).

Sheet 1 of 4

1. Billboard Notes (#7): correct sheet reference in parentheses (from Sheet
2 of 3 to Sheet 3 of 4).

Sheet 2 of 4

1. Provide the calcs related to the light arm support attachment (January
20, 2010) and include as part of the plan set.

2. Add notation clarifying that stiffener plates are only to be added to
the two uprights supporting the light arms and not to the other four
uprights.

Sheet 3 of 4

1. Notes (first set under Mean Lumen Calculation): add fourth note
indicating that only lamp to be used is that specified for the photometric
test detailed on Sheet 4 (Philips MS320/U/PS (Bulb size: ED-28))

2. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any change in circuits or breakers compared to existing panel, add notation
describing such change).

3. Provide circuit plan using Partial Plan View, one-line engineering plan
or otherwise, showing all junction boxes and other fixtures where wire
connections are made on the load side of the panel box and indicating the
circuit number as shown in the panel schedule.

4. Notes (Bullet #4): clarify that seven (7) is the total number of
junction boxes being installed or remaining on the load side of the panel
box.

5. Notes (Bullet #4), Partial Riser Diagram & Elevation: reduce the number
of #12 replacement conductors between the panel and first junction box from
seven (7) to four (4).

6. Notes (Bullets #4 & #5): indicate the number and type of each #12
conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground).

7. Notes (Bullet #5): reduce the number of #12 replacement conductors
between the first junction box and the second pair of junction boxes from
four (4) to three (3); show same on Elevation.

8. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

9. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

10. Notes: add notation specifying minimum and maximum distances below
junction boxes that flex cable drip loops/slack is to extend (or otherwise
provide appropriate limit on length of flex cables).

11. Elevation: show short, truncated run of second branch circuit off of
first junction box indicating the number and gauge of conductors and with a
note that lighting & electrical configuration for second face is same as
depicted for first face

12. Elevation: indicate location of flex cable loops between junction boxes
and light fixtures.

13. Elevation: depict existing ballasts with notation to be removed.

14. Add notation that as per Subparagraph 8.3.4 of the Stipulation a
special inspection is to be performed for metal halide lighting compliance
as provided for in Section 306 of the 1997 Uniform Administrative Code (or
any applicable successors or amendments thereto).

Sheet 4 of 4

1. Include manufacturer's spec sheet for Philips MS320/U/PS lamp specified
in photometric test.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2010 CPIERCE1 OUT TO CUSTOMER Completed