Permit Number - T10EL01284
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
08/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/09/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
resubmittal (8/3/10) for COT ID# 27 at 430 North Stone Avenue (T10EL01284).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. (Upper Box/Bullet #5): edit notation to read: "Special inspection
required prior to final inspection for installation of light fixture support
arms, light fixtures, shields, gaskets, and associated parts. Inspector to
verify that light fixtures are installed with shield in a horizontal
position so that no light is emitted above the horizontal plane and that
mean lumen output of the light fixtures does not exceed 1000 lumens per
horizontal foot of billboard face, as per the City of Tucson/Pima County
Outdoor Lighting Code and Subparagraph 8.3 of the City of Tucson-Clear
Channel Outdoor Stipulation (Pima County Superior Court No. C20003712)"
(current standardized form).

2. Notes (Bullet #5), Elevation & Partial Riser Diagram: reduce the number
of #12 replacement conductors between the panel and first junction box from
three (3) to two (2). [Comment #6, 6/21/10]

3. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain other than those depicted on
the plan. [Comment #7, 6/21/10]

4. Elevation & Partial Plan View: between the two junction boxes, edit
the wiring reference to "(2) #12 conductors & (1) #12 ground"
consistent with the change made to Notes (Bullet #4).

5. Panel Schedule, One-Line Diagram & Partial Plan View: reduce the number
of lighting circuits from two (2) to (1).

6. One-Line Diagram: include the timer controls. [See Comment #6, 6/21/10]

7. Elevation: indicate the locations where the SOOW cable is to be
installed with a note clarifying that those are the only locations where the
SOOW is to be installed (enclosed in the light arms supports between the two
junction boxes and the light fixtures). [See Comment #12, 6/21/10]

Sheet 4 of 4

No comments.