Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10EL01284
Parcel: 99999999B

Address:
430 N STONE AV

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01284
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: REFERENCE EXHIBIT 9 FOR REPLACEMENT OF ITEMS INDICATED ON SHEET 2. VERIFY NEW C6X10.5 MOUNTING BRACKETS, NEW 2.875" DIAMETER PIPES, NEW 2.375" DIAMETER PIPE LIGHT ARMS, NEW STIFFENER PLATES, AND NEW LIGHT FIXTURES ARE ALLOWED AS AUTHORIZED REPAIRS AND ALTERATIONS.
2. GENERAL: REPAIRS INDICATED FOR THIS BILLBOARD WILL BE DISCUSSED AT A FUTURE MEETING. APPROVAL OF THIS PROJECT WILL BE WITHHELD UNTIL THAT MEETING.
3. SHEET 1; BILLBOARD NOTES 7: REFERENCE IS MADE TO SHEET 2 OF 3. THERE ARE 4 TOTAL SHEETS. REVISE NOTE.
4. SHEET 1; BILLBOARD NOTES 9: REVIEW ALL PARAGRAPH REFERENCES LISTED AND VERIFY THOSE RELATE TO THE WORK DESCRIBED ON SHEET 2. REVISE REFERENCES AS REQUIRED.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10EL01284
430 N Stone Av

Electrical Plans denied, see comments from T10EL01287.

Ray T Majuta
City of Tucson PDSD
Elect Pln Ck
6/2/10
Ray.Majuta@tucsonaz.gov
06/23/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Review Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 27 at 430 North Stone Avenue (T10EL01284).

Sheet 1 of 3

1. Billboard Notes (#7): correct sheet reference in parentheses (from Sheet
2 of 3 to Sheet 3 of 4).

Sheet 2 of 3

1. Provide calcs for the light arm support attachment and justification
for adding stiffeners.

2. Add notation clarifying that stiffener plates are only to be added to
the two uprights supporting the light arms and not to the other four
uprights.

Sheet 3 of 3

1. Notes (first set under Mean Lumen Calculation): add fourth note
indicating that only lamp to be used is that specified for the photometric
test detailed on Sheet 4 (Philips MS320/U/PS (Bulb size: ED-28)).

2. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any change in circuits or breakers compared to existing panel, add notation
describing such change).

3. Provide circuit plan using Partial Plan View, one-line engineering plan,
or otherwise, showing all junction boxes or other fixtures where wire
connections are made on the load side of the panel box and indicating the
circuit number as shown in the panel schedule.

4. Notes (Bullet #3): reduce the number of junction boxes from three (3) to
two (2) and indicate that this is the total number to be installed or or
remaining on the load side of the panel box.

5. Notes (Bullets #4 & #5): indicate the number for of each type of #12
conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground).

6. Notes (Bullet #5), Elevation & Partial Riser Diagram: reduce the number
of #12 replacement conductors between the panel and first junction box from
four (4) to three (3).

7. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain other than those depicted on
the plan.

8. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used, including those associated with
the second circuit for the third and fourth light fixtures on each face, to
be removed.

9. Notes: add notation specifying maximum distance below junction boxes
that flex cable drip loops/slack is to extend (or otherwise provide
appropriate limit on length of flex cables).

10. Elevation: delete leftmost junction box.

11. Elevation: depict existing ballasts with notation to be removed.

12. Elevation: indicate location of flex cable loops between the two
junction boxes and light fixtures.

13. Add notation that a special inspection is to be performed for
compliance as provided for in Section 306 of the 1997 Uniform Administrative
Code (or any applicable successors or amendments thereto; as per
Subparagraph 8.3.4 of the Stipulation).

Sheet 4 of 4

1. Include manufacturer's spec sheet for Philips MS320/U/PS lamp specified
in photometric test.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2010 GERARDO BONILLA OUT TO CUSTOMER Completed