Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10EL01271
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01271
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/02/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: REFERENCE EXHIBIT 9 FOR REPLACEMENT OF ITEMS INDICATED ON SHEET 2. VERIFY NEW C6X10.5 MOUNTING BRACKETS, NEW 2.875" DIAMETER PIPES, NEW 2.375" DIAMETER PIPE LIGHT ARMS, NEW STIFFENER PLATES, AND NEW LIGHT FIXTURES ARE ALLOWED AS AUTHORIZED REPAIRS AND ALTERATIONS.
2. GENERAL: REPAIRS INDICATED FOR THIS BILLBOARD WILL BE DISCUSSED AT A FUTURE MEETING. APPROVAL OF THIS PROJECT WILL BE WITHHELD UNTIL THAT MEETING.
3. SHEET 1; BILLBOARD NOTES 7: REFERENCE IS MADE TO SHEET 2 OF 3. THERE ARE 4 TOTAL SHEETS. REVISE NOTE.
4. SHEET 1; BILLBOARD NOTES 9: REVIEW ALL PARAGRAPH REFERENCES LISTED AND VERIFY THOSE RELATE TO THE WORK DESCRIBED ON SHEET 2. REVISE REFERENCES AS REQUIRED.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10EL01271
6379 E Tanque Verde Rd

Electrical plans denied, see comments for T10EL01278.

Ray T Majuta
City of Tucson PDSD
Elect Pln Ck
6/2/10
Ray.majuta@tucsonaz.gov
06/30/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Comments below are for the lighting modification & electrical repair
submittal for COT ID# 122 at 6379 East Tanque Verde Road (T10EL01271).

Sheet 1 of 3

1. Billboard Notes (#7): correct sheet reference in parentheses (from Sheet
2 of 3 to Sheet 3 of 4).

Sheet 2 of 3

1. Provide the calcs related to the light arm support attachment (January
20, 2010) and include as part of the plan set.

2. Add notation clarifying that stiffener plates are only to be added to
the two uprights supporting the light arms and not to the other four
uprights.

Sheet 3 of 3

1. Notes (first set under Mean Lumen Calculation): add fourth note
indicating that only lamp to be used is that specified for the photometric
test detailed on Sheet 4 (Philips MS320/U/PS (Bulb size: ED-28))

2. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any change in circuits or breakers compared to existing panel, add notation
describing such change).

3. Provide circuit plan using Partial Plan View or otherwise, showing all
junction boxes or other fixtures where wire connections are made on the load
side of the panel box and indicating the circuit number as shown in the
panel schedule.

4. Notes (Bullet #3): clarify that the seven junction boxes to be
installed are the total number being installed or remaining on the load side
of the panel box.

5. Notes (Bullet #4), Elevation & Partial Riser Diagram: reduce the number
of #12 replacement conductors between the panel and first junction box from
seven (7) to four (4).

6. Notes (Bullet #6) & Elevation: reduce the number of #12 replacement
conductors between the first junction box and the second pair of junction
boxes from five (5) to three (3).

7. Notes (Bullets #4, #5 & #6): indicate the number and type of each #12
conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground).

8. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain on the load side of the panel
other than those depicted on the plan.

9. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used, including those associated with
the second circuit for the third and fourth light fixtures, to be removed.

10. Notes: add notation specifying maximum distance below junction boxes
that flex cable drip loops/slack is to extend (or otherwise provide
appropriate limit on length of flex cables).

11. Elevation: show short, truncated run of second branch circuit off of
first junction box indicating the number and gauge of conductors and with a
note that lighting & electrical configuration for second face is same as
depicted for first face

12. Elevation: indicate location of flex cable loops between junction boxes
and light fixtures.

13. Elevation: depict existing ballasts with notation to be removed.

14. Elevation & Partial Riser Diagram: resolve inconsistency as to diameter
of existing riser conduit (1/2" vs. 3/4").

15. Partial Plan View: show all junction boxes and conform circuitry to
Elevation and Notes (delete conductors between nose end junction boxes and
show junction boxes and conductors from junction box at near top of head
piece branching to junction boxes between two fixtures on each side).

16. Partial Plan View: delete reference to "MIN." as to ½" conduit.

17. Add notation that as per Subparagraph 8.3.4 of the Stipulation a
special inspection is to be performed for metal halide lighting compliance
as provided for in Section 306 of the 1997 Uniform Administrative Code (or
any applicable successors or amendments thereto).

Sheet 4 of 4

1. Include manufacturer's spec sheet for Philips MS320/U/PS lamp specified
in photometric test.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/25/2010 CINDY AGUILAR OUT TO CUSTOMER Completed