Permit Number: T10EL01262
Parcel: 99999999B

Address:
9501 E I10

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01262
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/03/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below comments on the lighting modification & electrical repair resubmittal
(7/30/10) for COT ID# 595 at 9501 East I-10 (T10EL01262).

Sheet 2 of 3

1. Panel Schedule: correct the new volt-amp entry for Circuit #1 and
associated sums; based on the ballast manufacturer's stated input watts (248
watts per two lamp fixture (F96T12HO)) and the 125% continuous load factor
that the EOR is including in the panel schedule, this figure should be 620
v-a for this circuit; if otherwise, provide the calculations as to how the
v-a entry was arrived at; these entries need to be standardized for all
pending and future panel schedules.

2. Panel Schedule & One-Line Diagram: include the volt-amps & circuitry for
the time controller respectively.

3. Panel Schedule: indicate the number of light fixtures under circuit
description for Circuit #1,.

4. Panel Schedule & One-Line Diagram: clarify whether the large enclosure
(designated a "junction box" in the original submittal) is a 206 panel or
not (its cabinet appears to have different dimensions than that for the
206); if not, make the appropriate changes, including the number of breaker
spaces and the cabinet dimensions shown in the panel schedule.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2010 CINDY AGUILAR OUT TO CUSTOMER Completed