Permit Number: T10EL01262
Parcel: 99999999B

Address:
9501 E I10

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01262
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/07/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting modification & electrical repair
submittal for COT ID# 595 at 9501 East I-10 (T10EL01262).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. No comments.

Sheet 2 of 3

1. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any proposed change in circuits or breakers compared to existing panel, add
notation describing such change).

2. Provide circuit plan using Partial Plan View or otherwise, showing
ballasts and any junction boxes or other fixtures where wire connections are
made on the load side of the panel box and indicating the circuit number as
shown in the panel schedule.

3.Notes (Bullet #6) & Elevation: indicate tee instead of junction box (or
explain why junction box is shown where there are no apparent wire
connections being made here; if ¾" tee is used, ¾" liquid tite is
permissible for this short run, rather than using ½" liquid tite with
reducers on each end, but change Bullets #7 & #11 and Elevation
accordingly).

4. Notes (Bullet #7): clarify this description, particularly as to the need
for the second sentence; it appears that there are two #18 wire bundles (six
wires each) that run from the panel box to the tee where they separate
without any wire connections and go on to each of the two fixtures (not just
the "remaining" fixture); if so, state more succinctly; if not, describe the
work more clearly.

5. Notes (Bullet #8): indicate that ½" EMT is being replaced in addition to
the ½" liquid tite being replaced; indicate the number and type of each #12
conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground).

6. Notes: add notation indicating total number of junction boxes on the
load side of the panel box.

7. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain other than those depicted on
the plan.

8. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

10. Elevation: add second arrow to indicate that both runs of wire between
the tee and light fixtures are (6) #18 wire.

11. Elevation: depict third existing ballast in center with notation to be
removed.

12. Elevation: below notation on new ballasts, indicate total number of
ballasts.

Sheet 3 of 3

No comments.
06/14/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2010 CPIERCE1 OUT TO CUSTOMER Completed