Permit Number: T10EL01260
Parcel: 14011021F

Address:
2502 E BENSON HY

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01260
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/01/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/05/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments on the lighting modification & electrical repair
resubmittal for COT ID# 13 at 2502 East Benson Highway (T10EL01260).

Sheet 1 of 4

No comments.

Sheet 2 of 4

1. Add notation clarifying that stiffener plates are only to be added to
the two uprights supporting the light arms and not to the other four
uprights. [Note: Sheet 2 was not resubmitted and this comment
remains from those provided on 6/7/10 on the initial submittal; applicant
has been adding this notation without fail on other resubmittals where this
comment was made].

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless otherwise indicated to Note #2 on THHN conductors.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/05/2010 CPIERCE1 OUT TO CUSTOMER Completed