Permit Number: T10EL01258
Parcel: 10701037A

Review Status: Active

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01258
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
09/29/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/30/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Comments below are for the lighting modification & electrical repair
resubmittal for COT ID# 172 at 1451 West Miracle Mile Strip (T10EL01258).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. Reduce number of circuits to one (1) per face.

2. If the electrical device attached to the rear (south) end of the upper
catwalk is to remain, this needs to be detailed on the plans.

Sheet 4 of 4

No comments.