Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC30days
Permit Number - T10EL01258
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: REFERENCE EXHIBIT 9 FOR REPLACEMENT OF ITEMS INDICATED ON SHEET 2. VERIFY NEW C6X10.5 MOUNTING BRACKETS, NEW 2.875" DIAMETER PIPES, NEW 2.375" DIAMETER PIPE LIGHT ARMS, NEW STIFFENER PLATES, AND NEW LIGHT FIXTURES ARE ALLOWED AS AUTHORIZED REPAIRS AND ALTERATIONS. 2. GENERAL: REPAIRS INDICATED FOR THIS BILLBOARD WILL BE DISCUSSED AT A FUTURE MEETING. APPROVAL OF THIS PROJECT WILL BE WITHHELD UNTIL THAT MEETING. 3. SHEET 1; BILLBOARD NOTES 7: REFERENCE IS MADE TO SHEET 2 OF 3. THERE ARE 4 TOTAL SHEETS. REVISE NOTE. 4. SHEET 1; BILLBOARD NOTES 9: REVIEW ALL PARAGRAPH REFERENCES LISTED AND VERIFY THOSE RELATE TO THE WORK DESCRIBED ON SHEET 2. REVISE REFERENCES AS REQUIRED. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 06/14/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | 1) PROVIDE PANEL SCHEDULE AND CLARIFY CIRCUITRY ON PARTIAL PLAN VIEW PP 3 0F 4. 2) PLEASE CLARIFY CONDUCTOR COUNT AT CONDUITS ON ELEVATION VIEW. DO YOU MEAN 6 #12 CONDUCTORS & 1 #12 GRD FROM PANEL BOX (3 #12 & #12 GRD FROM J-BOX TO EACH FACE THEN 2#12 W #12 TO EACH LIGHT)? ALSO PLEASE MAKE NOTE THAT ELEVATION VIEW IS TYPICAL FOR EACH FACE. |
| 06/30/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Comments below are for the lighting modification & electrical repair submittal for COT ID# 172 at 1451 West Miracle Mile Strip (T10EL01258). Sheet 1 of 3 1. Billboard Notes (#7): correct sheet reference in parentheses (from Sheet 2 of 3 to Sheet 3 of 4). 2. Overlay Map: conform the APN# to that shown in Billboard Notes (#3); delete former north-south property line at west edge of billboard; adjust the north property line to a more accurate location. Sheet 2 of 3 1. Provide the calcs related to the light arm support attachment (January 20, 2010) and include as part of the plan set. 2. Add notation clarifying that stiffener plates are only to be added to the two uprights supporting the light arms and not to the other four uprights. Sheet 3 of 3 1. Notes (first set under Mean Lumen Calculation): add fourth note indicating that only lamp to be used is that specified for the photometric test detailed on Sheet 4 (Philips MS320/U/PS (Bulb size: ED-28)) 2. Add panel schedule indicating circuits, breakers, and respective loads (as in submittals where replacement of service is indicated); if there is any change in circuits or breakers compared to existing panel, add notation describing such change). 3. Provide circuit plan using Partial Plan View or otherwise, showing all junction boxes or other fixtures where wire connections are made on the load side of the panel box and indicating the circuit number as shown in the panel schedule. 4. Notes (Bullet #3): clarify that the five (5) junction boxes to be installed are the total number being installed or remaining on the load side of the panel box. 5. Notes (Bullet #4), Elevation & Partial Riser Diagram: reduce the number of #12 replacement conductors between the panel and first junction box from seven (7) to four (4). 6. Notes (Bullet #5), Elevation & Partial Plan View: reduce the number of #12 replacement conductors between the first junction box and the second pair of junction boxes from four (4) to three (3); same for Bullet #6, conforming to Elevation. 7. Notes (Bullets #4, #5 & #6): indicate the number and type of each #12 conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground). 8. Notes: add notation that no junction boxes or other fixtures where wire connections are made to be installed or remain on the load side of the panel other than those depicted on the plan. 9. Notes: add notation that any excess fixtures, conduit, connectors, wiring, or breakers no longer being used, including those associated with the second circuit for the third and fourth light fixtures, to be removed. 10. Notes: add notation specifying maximum distance below junction boxes that flex cable drip loops/slack is to extend (or otherwise provide appropriate limit on length of flex cables). 11. Elevation: show short, truncated run of second branch circuit off of first junction box indicating the number and gauge of conductors and with a note that lighting & electrical configuration for second face is same as depicted for first face 12. Elevation: indicate location of flex cable loops between junction boxes and light fixtures. 13. Elevation: depict existing ballasts with notation to be removed. 14. Partial Plan View: show all junction boxes in conformity with the Elevation. 15. Partial Plan View: delete reference to "MIN." as to ½" conduit. 17. Add notation that as per Subparagraph 8.3.4 of the Stipulation a special inspection is to be performed for metal halide lighting compliance as provided for in Section 306 of the 1997 Uniform Administrative Code (or any applicable successors or amendments thereto). Sheet 4 of 4 1. Include manufacturer's spec sheet for Philips MS320/U/PS lamp specified in photometric test. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/25/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |