Permit Number: T10EL01257
Parcel: 99999999B

Address:
1299 E BENSON HY

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01257
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/20/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments for the lighting modification & electrical repair
resubmittal for COT ID# 5 at 1299 East Benson Highway (T10EL01257).

Sheet 1 of 5

No comments.

Sheet 2 of 5

1. In Scope of Work, clarify whether shims or any other parts are to be
added to realign uprights; if so, provide detail.

2. Provide detail on the wood sections to be removed and reinstalled,
including Z clips.

Sheet 3 of 5

1. Sheet 3 is missing; provide Sheet 3 or add note to Sheet 1 and
otherwise noting its absence.

Sheet 4 of 5

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless noted otherwise to Note #2 on THHN conductors.

3. Add standardized notation on special inspection requirement for metal
halide lighting installation.

Sheet 5 of 5

No comments.
10/20/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/21/2010 SUE REEVES APPROVAL SHELF Completed
10/21/2010 CINDY AGUILAR OUT TO CUSTOMER Completed