Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01257
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: REFERENCE EXHIBIT 9 FOR REPLACEMENT OF ITEMS INDICATED ON SHEET 2. VERIFY NEW C6X10.5 MOUNTING BRACKETS, NEW 2.875" DIAMETER PIPES, NEW 2.375" DIAMETER PIPE LIGHT ARMS, NEW STIFFENER PLATES, AND NEW LIGHT FIXTURES ARE ALLOWED AS AUTHORIZED REPAIRS AND ALTERATIONS.
2. GENERAL: REPAIRS INDICATED FOR THIS BILLBOARD WILL BE DISCUSSED AT A FUTURE MEETING. APPROVAL OF THIS PROJECT WILL BE WITHHELD UNTIL THAT MEETING.
3. SHEET 1; BILLBOARD NOTES 7: REFERENCE IS MADE TO SHEET 2 OF 3. THERE ARE 4 TOTAL SHEETS. REVISE NOTE.
4. SHEET 1; BILLBOARD NOTES 9: REVIEW ALL PARAGRAPH REFERENCES LISTED AND VERIFY THOSE RELATE TO THE WORK DESCRIBED ON SHEET 2. REVISE REFERENCES AS REQUIRED.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/07/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting modification & electrical repair
submittal for COT ID# 5 at 1299 East Benson Highway (T10EL01257).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Billboard Notes (#7): correct sheet reference in parentheses (from Sheet
2 of 3 to Sheet 3 of 4).

Sheet 2 of 3

1. Provide the calcs related to the light arm support attachment (January
20, 2010) and include as part of the plan set.

2. Add notation clarifying that stiffener plates are only to be added to
the two uprights supporting the light arms and not to the other four
uprights.

Sheet 3 of 3

1. Notes (first set under Mean Lumen Calculation): add fourth note
indicating that only lamp to be used is that specified for the photometric
test detailed on Sheet 4 (Philips MS320/U/PS (Bulb size: ED-28))

2. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any change in circuits or breakers compared to existing panel, add notation
describing such change).

3. Provide circuit plan using Partial Plan View or otherwise, showing all
junction boxes or other fixtures where wire connections are made on the load
side of the panel box and indicating the circuit number as shown in the
panel schedule.

4. Notes (Bullet #3): clarify that the seven junction boxes to be
installed are the total number being installed or remaining on the load side
of the panel box.

5. Notes (Bullet #4), Elevation & Partial Riser Diagram: reduce the number
of #12 replacement conductors between the panel and first junction box from
seven to four (two pair of 320-watt lamps do not justify third and fourth
circuits).

6. Notes (Bullet #5) & Elevation: reduce the number of #12 replacement
conductors between the first junction box and the second pair of junction
boxes from five to three (two pair of 320-watt lamps do not justify third
and fourth circuits).

7. Notes (Bullets #4, #5 & #6): indicate the number and type of each #12
conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground).

8. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain other than those depicted on
the plan.

9. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used, including those associated with
the second circuit for the third and fourth light fixtures, to be removed.

10. Notes: add notation specifying maximum distance below junction boxes
that flex cable drip loops/slack is to extend (or otherwise provide
appropriate limit on length of flex cables).

11. Elevation: show short, truncated run of second branch circuit off of
first junction box indicating the number and gauge of conductors and with a
note that lighting & electrical configuration for second face is same as
depicted for first face

12. Elevation: depict loops of flex cable between the two junction boxes
and light fixtures.

13. Elevation: depict existing ballasts with notation to be removed.

14. Elevation & Partial Riser Diagram: resolve inconsistency as to diameter
of existing riser conduit (1/2" vs. 3/4").

15. Partial Plan View: delete reference to "MIN." as to ½" conduit.

Sheet 4 of 4

1. Include manufacturer's spec sheet for Philips MS320/U/PS lamp specified
in photometric test.
06/14/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) CLARIFY # OF CONDUCTORS PP 3 OF 4. YOU ARE CALLING OUT 7 NEW CONDUCTORS, DO YOU MEAN 6 #12 & 1 #12 GRD? ALSO YOU APPEAR TO BE GOING FROM 7 TO 5 THEN TO 6 CONDUCTORS ON THE PLAN, PLEASE CLARIFY.

2) PLEASE PROVIDE PANEL SCHEDULE

Final Status

Task End Date Reviewer's Name Type of Review Description
09/13/2010 CPIERCE1 OUT TO CUSTOMER Completed