Permit Number: T10EL01172
Parcel: 99999999B

Address:
1677 N WILMOT RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01172
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
08/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/02/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
resubmittal for COT ID# 123 at 1677 Wilmot Road (T10EL01172).

Sheet 1 of 3

No comments.

Sheet 2 of 3

No comments.

Sheet 3 of 3

1. Notes (Bullet #3), Elevation & Partial Riser Diagram: reduce the number
of #12 replacement conductors between the panel and first junction box from
six (6) to three (3).

2. Notes (Bullet #5), Elevation & Partial Plan View: reduce the number of
#12 replacement conductors between the first junction box and the second
pair of junction boxes from four (4) to two (2).

3. Elevation, Partial Plan View, One-Line Diagram & Panel Schedule: reduce
number of lighting circuits from four (4) to (2).

4. Elevation: indicate location of SOOW between the two junction boxes and
light fixtures and clarify that this is the only location where flexible
cable is to be used.

5. SOOW Product Data Sheet: clarify why SOOW is being used instead of SO
since cable will not be exposed.

6. Panel Schedule: correct volt-amp entry for 320 watt light fixtures
(entries appear to correspond to 400-watt fixtures).

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/22/2010 SUE REEVES OUT TO CUSTOMER Completed
09/22/2010 SUE REEVES REJECT SHELF Completed