Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10EL01172
Parcel: 99999999B

Address:
1677 N WILMOT RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL01172
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/25/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL: REFERENCE EXHIBIT 9 FOR REPLACEMENT OF ITEMS INDICATED ON SHEET 2. VERIFY NEW C6X10.5 MOUNTING BRACKETS, NEW 2.875" DIAMETER PIPES, NEW 2.375" DIAMETER PIPE LIGHT ARMS, NEW STIFFENER PLATES, AND NEW LIGHT FIXTURES ARE ALLOWED AS AUTHORIZED REPAIRS AND ALTERATIONS.
2. GENERAL: REPAIRS INDICATED FOR THIS BILLBOARD WILL BE DISCUSSED AT A FUTURE MEETING. APPROVAL OF THIS PROJECT WILL BE WITHHELD UNTIL THAT MEETING.
3. SHEET 1; BILLBOARD NOTES 7: REFERENCE IS MADE TO SHEET 2 OF 3. THERE ARE 4 TOTAL SHEETS. REVISE NOTE.
4. SHEET 1; BILLBOARD NOTES 9: REVIEW ALL PARAGRAPH REFERENCES LISTED AND VERIFY THOSE RELATE TO THE WORK DESCRIBED ON SHEET 2. REVISE REFERENCES AS REQUIRED.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
06/16/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Comments below are for the lighting modification & electrical repair
submittal for COT ID# 123 at 1677 Wilmot Road (T10EL01172).

Sheet 1 of 3

1. Billboard Notes (#7): correct sheet reference in parentheses (from Sheet
2 of 3 to Sheet 3 of 4).

Sheet 2 of 3

1. Provide the calcs related to the light arm support attachment (January
20, 2010) and include as part of the plan set.

2. Add notation clarifying that stiffener plates are only to be added to
the two uprights supporting the light arms and not to the other four
uprights.

Sheet 3 of 3

1. Notes (first set under Mean Lumen Calculation): add fourth note
indicating that only lamp to be used is that specified for the photometric
test detailed on Sheet 4 (Philips MS320/U/PS (Bulb size: ED-28)).

2. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any change in circuits or breakers compared to existing panel, add notation
describing such change).

3. Provide circuit plan using Partial Plan View, one-line engineering plan,
or otherwise, showing all junction boxes or other fixtures where wire
connections are made on the load side of the panel box and indicating the
circuit number as shown in the panel schedule.

4. Notes (Bullet #3, Elevation & Partial Riser Diagram): indicate ½"
replacement conduit.

5. Notes (Bullet #4), Elevation & Partial Riser Diagram: reduce the number
of #12 replacement conductors between the panel and first junction box from
seven to four (two pair of 320-watt lamps do not justify third and fourth
circuits).

6. Notes (Bullet #5) & Elevation: reduce the number of #12 replacement
conductors between the first junction box and the second pair of junction
boxes from five to three (two pair of 320-watt lamps do not justify third
and fourth circuits).

7. Notes (Bullets #3 & #6): indicate the number for of each type of #12
conductor in parentheses (e.g., (1) hot, (1) neutral & (1) ground).

8. Notes: add notation that no junction boxes or other fixtures where wire
connections are made to be installed or remain other than those depicted on
the plan.

9. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used, including those associated with
the second circuit for the third and fourth light fixtures on each face, to
be removed.

10. Notes: add notation specifying maximum distance below junction boxes
that flex cable drip loops/slack is to extend (or otherwise provide
appropriate limit on length of flex cables).

11. Elevation: show short, truncated run of second branch circuit off of
first junction box indicating the number and gauge of conductors and with a
note that lighting & electrical configuration for second face is same as
depicted for first face.

12. Elevation: indicate location of flex cable loops between the two
junction boxes and light fixtures.

13. Add notation that a special inspection is to be performed for
compliance as provided for in Section 306 of the 1997 Uniform Administrative
Code (or any applicable successors or amendments thereto; as per
Subparagraph 8.3.4 of the Stipulation).

14. Provide manufacturer, model number, and load/lamp data for illuminated
imprint.

Sheet 4 of 4

1. Include manufacturer's spec sheet for Philips MS320/U/PS lamp specified
in photometric test.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2010 GERARDO BONILLA OUT TO CUSTOMER Completed