Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL01037
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01037
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/13/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/13/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/14/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments on the lighting relocation & electrical repair
resubmittal (9/8/10) for COT ID# 49 at 713 West Speedway Boulevard
(T10EL01037).

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Panel Schedule: correct the volt-amp entries for Circuits #1 and #3 and
associated sums; based on the ballast manufacturer's stated input watts (248
watts per two lamp fixture (F96T12HO)) and the 125% continuous load factor
that the EOR has been including in the panel schedule, this figure should be
310 v-a for each circuit; if otherwise, provide the calculations as to how
the v-a entry was arrived at; these entries need to be standardized for all
pending and future panel schedules. Add continuous load notation as on
other submittals, if applicable.

2. Electrical Riser Diagram (left view): in the ¾" EMT conduit between the
two ballast, it appears that the number of #18 conductors in this run should
be six (6), rather than the twelve (12) designated.

3. Elevation: panel is designated as 206MPRS, inconsistent with the
manufacturer's literature sheet where 206PROG is shown; resolve this
difference..

4. Partial Plan View: add circuit numbers.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/14/2010 SUE REEVES APPROVAL SHELF Completed
10/14/2010 CPIERCE1 OUT TO CUSTOMER Completed