Permit Number: T10EL01037
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01037
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/01/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting relocation & electrical repair
submittal for COT ID# 49 at 713 West Speedway Boulevard (T10EL01037).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Billboard Notes (#3) & Title Block: delete APN# entered and indicate
location in ADOT right-of-way (former parcel number for this location may be
included as well).

2. Title Block: Project Number: as it appears that the parcel number is
being used to identify the project, it would appear that this number should
be changed as well.

Sheet 2 of 3

1. Notes: add notation on installation of conduit between the new panel
box and ballasts, including conduit size and number of conductors.

2. Notes: add notation that no junction boxes to be used other than for
wire connection purposes and that no junction boxes to be installed or
remain other than those depicted on the plan.

3. Notes: add notation that number of #12 replacement conductors indicated
includes ground wire.

4. Elevation: indicate the size of conduit between the panel box and
ballasts and number and gauge of conductors.

5. Elevation: depict the tee where the two bundles of #18 ballast wire will
branch & how the tee is to connect to the new ¾" rigid conduit.

6. Provide standard configuration for total service replacement, showing
all connectors used (nipples, tees, service
elbows, etc) and conductors. [Note: not required, but as first requested
for resubmittal on T10EL00530 (2601 E. Grant), may be used as a standard
detail if provided; three views preferred, but one view may suffice if all
parts in one plane as in Sheet 2 resubmittal for T10EL00752; see also Sheet
2 of resubmittal for T10EL00836 (6501 S. Nogales) for a partial example in
three-dimensional form].

Sheet 3 of 3

1. Provide top and end views detailing how two bundles of #18 ballast wire
to branch and connect to the new ¾" support arm conduit.

2. Side View: add dimension between top stringer and top of upright/face
panel (alternatively, either indicate uppermost stringer as "Top Stringer"
or depict all four stringers).

3. Indicate mounting detail furthest to right on plan as side view
(similarly as other two have been designated "rear elevation view" & "top
view").

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/08/2010 SUE REEVES REJECT SHELF Completed