Permit Number: T10EL01036
Parcel: 99999999B

Address:
1893 W PRINCE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01036
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
06/25/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
06/28/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the lighting relocation & electrical repair
resubmittal for COT ID# 409 at 1893 West Prince Road (T10EL01036).

Sheet 2 of 3

1. The resubmittal was not responsive to Comment #1. As an alternative to
denial, PDSD staff may add a notation to the plan or enter a notice
administratively that installation of the new lamps shown on plan (Sylvania
F96T12/CW/VHO/SL) to be confirmed by field inspection prior to final
inspection approval (applicable only to this 3-fixture/5-lamp
configuration).

2. Add PDSD staff notation to the plan or enter notice administratively
that installation of the number and gauge of conductors shown on plan
between panel box and first junction box to be confirmed by field inspection
prior to final inspection approval.

3. Comment for future reference: Elevation: the branch junction box was
changed from single gang to double gang, but not clouded; all changes to the
plan need to be clouded; if this change is not necessary to accommodate the
wire connections as to NEC minimum capacity, then it should remain single
gang.

Sheet 3 of 3

1. The resubmittal was not responsive to Comment #1. As an alternative to
denial, PDSD staff may add a notation to the plan or enter a notice
administratively that installation of the new lamps shown on plan (Sylvania
F96T12/CW/VHO/SL) to be confirmed by field inspection prior to final
inspection approval (applicable only to this 5-lamp configuration).

FIN.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2010 CPIERCE1 OUT TO CUSTOMER Completed
09/01/2010 SUE REEVES REJECT SHELF Completed