Permit Number: T10EL01036
Parcel: 99999999B

Address:
1893 W PRINCE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC10days

Permit Number - T10EL01036
Review Name: BILLBOARD-BLDG/ELEC10days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/06/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
05/19/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting relocation & electrical repair
submittal for COT ID# 409 at 1893 West Prince Road (T10EL01036).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. Notes (3rd Bullet): add notation that Sylvania F96T12/CW/VHO or other
VHO lamp with a higher mean lumen rating than 9604 may not be installed as a
substitute on this billboard. Sylvania F96T12/CW/VHO/SS (9100 mean lumens)
is the preferred lamp for this 5-lamp (per face) installation.

2. Notes (5th Bullet) & Electrical Riser diagram: resolve discrepancy as to
whether existing EMT is 1/2" or 3/4".

3. Notes (6th Bullet): indicate three junction boxes below the set of
ballasts for each face (instead of four) and one single junction box for
opposite face light fixture branch.

4. Notes: Add notation that no junction boxes other than those depicted to
be installed.

5. Clarify that leftmost junction box depicted is single location where
branch occurs for two light fixture circuits; provide the specific location
of this junction box (current location is much lower).

6. Elevation: depict transition coupling/reducer between 1/2" liquid tite
and 3/4" new rigid conduit.

Sheet 3 of 3

1. Description of Existing Lamp: add notation that Sylvania F96T12/CW/VHO
or other VHO lamp with a higher mean lumen rating than 9604 may not be
installed on this billboard. Sylvania F96T12/CW/VHO/SS (9100 mean lumens) is
the preferred installation for this 5-lamp (per face) installation.

2. Side View: add dimension between top stringer and top of upright/face
panel (alternatively, either indicate uppermost stringer as "Top Stringer"
or depict all four stringers).

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2010 CPIERCE1 OUT TO CUSTOMER Completed