04/16/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied 1) PLEASE INDICATE CONDUIT SIZES, TYPES AND RUN DISTANCE.

2) SHOW ALL SERVICE EQUIPMENT GROUNDING AND BONDING.

3) PROVIDE FAULT CURRENTS AND EQUIPMENT RATINGS.

4) PLANS FOR 400 AMP SERVICE REQUIRED TO BE PREPARED BY REGISTERED ENGINEER.