Permit Number: T10EL00910
Parcel: 120062070

Address:
4103 S 6TH AV

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00910
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Billboard: T10EL00910 , 4103 S th Av

Electrical denied for the following:

1.Provide information on transition for 1/2" to 3/4" on Sheet 2 of 3 on Elevation, how is it done ?
2. Upgrading of service to be approved by Glenn Moyer.

Ray T Majuta, Elect Pln Ck
PDSD of Tuc,
4/24/10
520-837-4988
05/03/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting modification & electrical repair
resubmittal for COT ID# 194 at 4103 South 6th Avenue (T10EL00910).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Comment for future reference only: Billboard Notes (#5): change "Faces"
to "faces".
2. Comment for future reference only: Billboard Notes (#11): delete comma
after "relocated".
3. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Site Plan".
4. Comment for future reference only: delete "COT Activity No. __________"
under the title block (as per 4/27/10 meeting; retain for resubmittals only,
with assigned number filled in).

Sheet 2 of 3

1. Title Block: change title to "Lighting Modification and Electrical
Repair Plan" (do not include quotation marks).
2. Electrical Riser Diagram: provide a standard configuration relative to
the I-beam where the entire service is being replaced on twin-beam poster
panels (with or without backing panel; able to include second ballast for
double-faced billboard; add top view if appropriate; see comments for
T10EL00530/COT ID# 439).
3. Panel Block: delete entry for spare circuit.
4. Enter T10EL00910 into COT Activity No. blank.

Sheet 3 of 3

1. Title Block: change title to "Lighting Modification and Electrical
Repair Plan" (do not include quotation marks).
2. Delete vertical extension of each light arm support from just below
second stringer from the top to third stringer from the top and delete added
clamp on each third stringer from the top; move horizontal run of ½" EMT
conduit and associated elbows accordingly; all as per 4/27/10 meeting).
3. Enter T10EL00910 into COT Activity No. blank.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/12/2010 CPIERCE1 OUT TO CUSTOMER Completed
08/12/2010 SUE REEVES REJECT SHELF Completed