Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10EL00909
Parcel: 99999999B

Address:
4862 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00909
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/19/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
05/19/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
06/14/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Comments below are for the second resubmittal for electrical repair for COT
ID# 82 at 4862 East 22nd Street (T10EL00909).

Sheet 2 of 2

1. Elevation: clarify where branch for east face circuit is to occur; if in
ballast area (presumably the case), delete junction box depicted and change
accordingly in Notes (Bullet #4); if at junction box, indicate three
conductors between junction box and ballasts instead of four.

2. Notes (Bullet #4): clarify where the branch for the east face circuit is
to occur (i.e., at some point after four conductors are indicated on
Elevation).

Comments for future reference, preferably revised on this plan:

3. Add panel schedule indicating circuits, breakers, and respective loads
(as in submittals where replacement of service is indicated); if there is
any change in circuits or breakers compared to existing panel, add notation
describing such change).

4. Provide circuit plan using Partial Plan View or otherwise, showing
ballasts and any junction boxes or other fixtures where wire connections are
made on the load side of the panel box and indicating the circuit number for
each fixture or device shown in the panel schedule.

5. Notes (Bullet #4): indicate the number and type of each #12 conductor in
parentheses (e.g., (1) hot, (1) neutral & (1) ground).

6. Notes (Bullet #6): indicate that the junction boxes being installed or
remaining on the load side of the panel box is the total number.

7. Notes: add notation that no junction boxes or other fixtures where wire
connections are made on the load side of the panel box to be installed or
remain other than those depicted on the plan.

8. Notes: add notation that any excess fixtures, conduit, connectors,
wiring, or breakers no longer being used to be removed.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/01/2010 CPIERCE1 OUT TO CUSTOMER Completed