Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10EL00909
Parcel: 99999999B

Address:
4862 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00909
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Billboard: T10EL00909, 4862 E 22ND ST

Electrical denied for following:

1. How will transition be made on 1/2" conduit to 3/4" conduit, on Sheet 2 of 3, on Elevation ?

Ray T Majuta, El Pln Ck,
PDSD, C of Tuc,
4/24/10
520-837-4988
05/03/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting modification & electrical repair
submittal for COT ID# 82 at 4862 East 22nd Street (T10EL00909).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Comment for future reference only: Billboard Notes (#5): change "Faces"
to "faces".
2. Comment for future reference only: Billboard Notes (#11): delete comma
after "relocated".
3. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Site Plan".

Sheet 2 of 3

1. Title Block: enter T10EL00909 in the COT Activity No. blank and delete
quotation marks.
2. Title Block: change title to "Lighting Modification
and Electrical Repair Plan" and delete quotation marks.
3. Clarify the purpose of the ½" EMT run and junction box past the two
ballasts and furthest away from the meter.

Sheet 3 of 3

1. Comment for future reference only: Title Block: enter T10EL00909 in the
COT Activity No. blank and delete quotation marks.
2. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Plan" (do not add quotation
marks).
3. Comment for future reference only: Description of Existing Lamp: change
"Existing" to "New".
4. Comment for future reference only: Mounting Details: assure that
vertical position of unistrut matches in all views and that the three views
are reasonably scaled to each other; also bring scale of 6" wood stringer
more into scale with 7" unistrut and delete dotted line in Mounting Detail -
Rear Elevation View.
5. Comment for future reference only: Side View: add dimension between top
stringer and top of upright/face panel (alternatively, depict all four
stringers).

Final Status

Task End Date Reviewer's Name Type of Review Description
05/14/2010 CPIERCE1 OUT TO CUSTOMER Completed
05/14/2010 SUE REEVES REJECT SHELF Completed