Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
08/03/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
09/08/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the lighting modification & electrical repair second
resubmittal for COT ID# 473 at 2921 North 1st Avenue (T10EL00908).

Sheet 2 of 3

1. Notes (Bullet #9): delete this note as its need has been superseded by
the separate reference to the ground wire now bring used throughout the
plan.

2. Panel Schedule: correct the new volt-amp entries for Circuits #1 and #3
and associated summations (in response to 5/31/10 Comment #8); based on the
ballast manufacturer's stated input watts (248 watts per two lamp fixture
(F96T12HO)) and the 125% continuous load factor that the EOR is including in
the panel schedule, this figure should be 620 v-a for each of those
circuits; if otherwise, provide the calculations as to how the v-a entries
were arrived at; these entries need to be standardized for all pending and
future panel schedules.

3. Elevation: for the wiring between the panel box and first ballast,
delete the designation of four (4) conductors as it has been superseded by
the separate reference to the ground wire now in the new clouded
designation below.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/08/2010 GERARDO BONILLA REJECT SHELF RECEIVED