| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/21/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/23/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Billboard: T10EL00908 , 2921 N 1st Av Electrical denied for following: 1. Provide information on transition to be made from 1/2" liquid tite to 3/4" conduit. 2. Glenn Moyer to approve allowing Service Upgrade. Ray T Majuta, Elect Pln Ck, PDSD< C of Tuc, 4/24/10 520-837/4988 |
| 05/03/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | Please find below comments on the lighting modification & electrical repair submittal for COT ID# 473 at 2921 North 1st Avenue (T10EL00908). Mark Mayer Billboard Review Committee 3361 East 23rd Street Tucson, Arizona 85713 520.326.4522 Sheet 1 of 3 1. Comment for future reference only: Billboard Notes (#5): change "Faces" to "faces". 2. Comment for future reference only: Billboard Notes (#11): delete comma after "relocated". 3. Comment for future reference only: Title Block: change title to "Lighting Modification and Electrical Repair Site Plan". 4. Comment for future reference only: delete "COT Activity No. __________" under the title block (as per 4/27/10 meeting; retain for resubmittals only at revised location). Sheet 2 of 3 1. Title Block: enter T10EL00908 in COT Activity No. blank. 2. Title Block: change title to "Lighting Modification and Electrical Repair Plan" (do not add quotation marks). 3. Note (Bullet #2): indicate ¾" rigid conduit as "new". 4. Note (Bullet #3): indicate HO lamp with matching specifications 5. Note (Bullet #5): indicate ballast to match HO (800 ma). 6. Panel Block: delete entry for spare breaker. Sheet 3 of 3 1. Title Block: enter T10EL00908 in COT Activity No. blank. 2. Title Block: change title to "Lighting Modification and Electrical Repair Plan" (do not add quotation marks). 3. Mounting Detail (3rd on right): indicate as side view & conform vertical location of unistrut to Mounting Detail Rear Elevation (the former shows the unistrut top flush with the stringer top while the latter shows the unistrut top one inch (+/-) below the stringer top); also bring scale of 6" wood stringer more into scale with 7" unistrut and three details more into scale with each other. 4. Description of Existing Lamp: change "Existing" to "New" and indicate HO lamp with matching specifications. 5. Description of Existing Ballast: indicate ballast that matches HO (800 ma). 6. Side View: add dimension between top stringer and top of upright/face panel (alternatively, depict all four stringers). |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/21/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 05/21/2010 | SUE REEVES | REJECT SHELF | Completed |