Permit Number: T10EL00908
Parcel: 107120140

Address:
2921 N 1ST AV

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL00908
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/23/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Billboard: T10EL00908 , 2921 N 1st Av


Electrical denied for following:
1. Provide information on transition to be made from 1/2"
liquid tite to 3/4" conduit.
2. Glenn Moyer to approve allowing Service Upgrade.

Ray T Majuta, Elect Pln Ck,
PDSD< C of Tuc,
4/24/10
520-837/4988
05/03/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Please find below comments on the lighting modification & electrical repair
submittal for COT ID# 473 at 2921 North 1st Avenue (T10EL00908).

Mark Mayer
Billboard Review Committee
3361 East 23rd Street
Tucson, Arizona 85713
520.326.4522

Sheet 1 of 3

1. Comment for future reference only: Billboard Notes (#5): change "Faces"
to "faces".
2. Comment for future reference only: Billboard Notes (#11): delete comma
after "relocated".
3. Comment for future reference only: Title Block: change title to
"Lighting Modification and Electrical Repair Site Plan".
4. Comment for future reference only: delete "COT Activity No. __________"
under the title block (as per 4/27/10 meeting; retain for resubmittals only
at revised location).

Sheet 2 of 3

1. Title Block: enter T10EL00908 in COT Activity No. blank.
2. Title Block: change title to "Lighting Modification and Electrical
Repair Plan" (do not add quotation marks).
3. Note (Bullet #2): indicate ¾" rigid conduit as "new".
4. Note (Bullet #3): indicate HO lamp with matching specifications
5. Note (Bullet #5): indicate ballast to match HO (800 ma).
6. Panel Block: delete entry for spare breaker.

Sheet 3 of 3

1. Title Block: enter T10EL00908 in COT Activity No. blank.
2. Title Block: change title to "Lighting Modification and Electrical
Repair Plan" (do not add quotation marks).
3. Mounting Detail (3rd on right): indicate as side view & conform vertical
location of unistrut to Mounting Detail Rear Elevation (the former shows the
unistrut top flush with the stringer top while the latter shows the unistrut
top one inch (+/-) below the stringer top); also bring scale of 6" wood
stringer more into scale with 7" unistrut and three details more into scale
with each other.
4. Description of Existing Lamp: change "Existing" to "New" and indicate HO
lamp
with matching specifications.
5. Description of Existing Ballast: indicate ballast that matches HO (800
ma).
6. Side View: add dimension between top stringer and top of upright/face
panel (alternatively, depict all four stringers).

Final Status

Task End Date Reviewer's Name Type of Review Description
05/21/2010 CPIERCE1 OUT TO CUSTOMER Completed
05/21/2010 SUE REEVES REJECT SHELF Completed